o Time to Produce Static Pressure (sec): Enter the length of time to reach target pressure
when minimum ventilation fan cycle is on.
o Attic Advance Opening Time (sec): Define the amount of time for the attic inlets to open
before minimum vent cycling fans turn on.
3.7.4 M
S
T
ULTI
TAGE
UNNEL
When in static pressure mode and employing multiple tunnel curtains, Platinum Touch/Rotem One Touch
can open the curtains in sequence. Opening the tunnel curtains commences when the target static
pressure is reached and the controller signals to the tunnel machine to operate the curtains. Platinum
Touch/Rotem One Touch opens the first tunnel curtain (as defined in the relays) to the user defined
level. If additional ventilation is required, the second tunnel curtain opens. This process continues for
each defined curtain.
As pressure falls, the process is reversed; curtains close in progression starting with the last curtain.
To set up Multi Stage Tunnel Curtains:
1. In System >
Relay Layout
2. In System > Levels of Ventilation > Vent & Curtain Levels, define the opening levels for each curtain.
3. In Static Pressure > Tunnel Ventilation, define the target pressure.

3.8 Cool Pad

This menu sets the cool pad operating conditions.
NOTE
Cool Pads only operate when the controller is in tunnel mode. For example, if the cool pad is
set to run at Level 8 and the tunnel mode begins at level 10, the cool pad remains inoperative.
1. In System > Relay Layout, define relays as Cool Pad.
2. Go to Control > Cool Pad.
3. Define:
Day: Set the growth day in this field.
Start Time: The cool pad begins operating at this time.
End Time: The cool pad ceases to operate at this time.
o It is possible to set multiple start and stop times for a single day.
o In the screen above, growth day jumps from day 1 to day 5, the cool pad continues to
work according to day 1 settings from growth day 1 through growth day 5.
Tunnel Diff: Set the band above the target temperature so that the cool pad begins to operate at
this temperature.
C
URTAINS
define more than one relay as tunnel curtain (open and close).
© Munters AB, 2018
38