The information contained herein has been prepared by qualified experts within Munters. While we believe the information is accurate and complete, we make no warranty or representation for any particular purposes. The information is offered in good faith and with the understanding that any use of the units or accessories in breach of the directions and warnings in this document is at the sole discretion and risk of the user.
7. Calibrate temperature, humidity, ventilation, static pressure, feed, water, read/save to plug. 8. Install sensors, devices, communication, etc. 2.2 Selecting the Mode Farm Premium runs in four modes: Broiler, Layer, Breeders, and Pigs. To select the mode: 1. Disconnect the power cable from the power source.
Farm Premiumreminds you. When you press Enter to acknowledge the reminder, the Farm Premium logs it in the Table of Events. Target Temp. Band: The size of the target temperature zone. This "Happy Zone” is between •...
Cool Down Fast Response (Deg.): Set a limit to the maximum degrees per minute of cooling. • If Average Temperature drops more than this in one minute, the Farm Premium decreases ventilation one level to avoid overshooting. NOTE: Avoid making this parameter too small or the normal temperature variation caused by timer fans reduces the ventilation level.
Page 18
If the temperature continues to drop, heaters operate for longer periods of time, up to the • Maximum On Time (defined in Levels of Ventilation). Farm Premium automatically generates a curve. • In this example: Temperature Curve Heat Off is 78°.
Page 19
3.1.4 V ARIABLE EATER EFINITIONS The Farm Premium Controller enables configuring up to eight variable heaters. The heater output changes according to the output of a 0 – 10 VDC device. Install at least one analog output card. To configure the variable heaters: 1.
Page 21
When the temperature falls below the user-defined point, the heaters begin operating at their • minimum output. After the response time passes, Farm Premium checks the temperature. If it is still below the • defined point, Farm Premium increases the voltage by a certain amount (this amount of the increase cannot be changed).
VARIABLE FLOOR HEATER Low Diff Below Heat Tmp. High Diff Below Heat Tmp. Farm Premium Controllers enable configuring up to two variable floor heaters. The output of the heaters changes as the temperature increases or decreases. Install at least one analog output card.
Proportional Heat Refer to the above sections for further information on these modes. 3.2 Introduction to Humidity, Ammonia, and CO2 Treatment Farm Premium provides various options to controlling the humidity, CO2, and ammonia levels. None: No treatment is provided. •...
(outdoor sensor is for information only). When using more than one sensor, Farm Premium begins treatments based on the average. 2. If required, go to Service > Humidity Calibration, and calibrate the sensors (refer to Humidity Calibration, page 95).
Once you have entered the ventilation levels, use the Min/Max to select the range of levels to apply to your situation. Typically, Farm Premium increases the minimum ventilation level as litter conditions deteriorate and the birds require greater amounts of fresh air. You can also restrict the maximum level to prevent excess airflow on young birds.
The By Weight option enables controlling the minimum air flow depending on the number of birds, their weight and the current outside temperature. When using the Weight option, Farm Premium takes several parameters and calculates the air speed, level of ventilation and cycle time needed to supply the required volume.
Page 30
Ventilation. During this time, the fans supply the required volume of air at the minimum ventilation level required. Farm Premium adjusts the minimum ON time and OFF time as needed. If the fans cannot supply the required volume at a particular level of ventilation, Farm Premium automatically adjusts the minimum ventilation level.
Level: Displays the current, minimum and maximum level of ventilation. • NOTE: If the current level is below the minimum required level, Farm Premium displays an alarm “Below Min Air”. Cycle On/Off: Displays the current, minimum and maximum fan on and off times.
Page 32
Low Static Pressure Alarm: Set alarm for low static pressure. If you disable it by setting zero, • the Farm Premium warns you and enters a record in the Table of Events. High Static Pressure Alarm: Set alarm for high static pressure.
Opening the tunnel curtains commences when the target static pressure is reached and the controller signals to the tunnel machine to operate the curtains. Farm Premium opens the first tunnel curtain (as defined in the relays) to the user defined level. If additional ventilation is required, the second tunnel curtain opens.
4 Device Menu The Farm Premium can have many closely spaced levels of ventilation enabling it to find the optimum average airflow for the poultry facility. Many of the levels are at exactly the same temperature setting, so there may be a question as to how the Farm Premium chooses the correct level.
4.1.2 W HILL Farm Premium can take into consideration the wind chill factor when making certain calculations related to the temperature. In effect, the wind chill factor acts as the temperature differential. When enabled, Farm Premium determines the “calculated temperature (actual temperature – wind chill temperature) and...
• negative differential temperatures. o Note the settings for Day 14. The Farm Premium uses the maximum temperature differential that applies to choose the correct settings. To Humidity: Set maximum humidity allowed before stopping cool pad. You can enter 100%.
Difference Between Cool Pads Stage: Farm Premium supports four cooling pad stages. The • controller activates the first stage when the temperature reaches the Tunnel Temperature (Control > Temperature Curve) plus the Tunnel Differentiation (set in the Cool Pad screen).
Page 48
NOTE: Munters recommends keeping this function set at the default setting (No). Difference between Foggers Stage: Farm Premium supports four fogging stages. The • controller activates the first stage when the temperature reaches the Target Temperature (Control >...
Page 55
Install | Relay Layout. Your selections will likely be • different from the example above. The Farm Premium does not allow certain selections for the emergency functions. Differential: The difference from target temperature at which the device operates during •...
(manual or solenoid according to the mode installed). Farm Premium enables controlling the water cycle times using relays and controlling the water pressure using analog input and output sensors. The two methods are complimentary. A user can use either one alone or both.
Wind and Rain Effect 4.13.1 H ATURAL ENTILATION For Farm Premium to switch to Natural Ventilation: Natural Ventilation works only during the defined growth days and daily schedule. • The temperature inside the chicken house must be within the inside temperature band.
Page 60
• Minimum Wind Speed for Tunnel Temp: When the unit is in Natural Mode, if the temperature • rises above the Tunnel Temperature, Farm Premium switches to Tunnel mode unless the wind speed is above the speed set here. NOTE: The above three parameters require installing and configuring a wind speed sensor.
Natural Program Status. 4.13.6.1 Ventilation is Not in Natural Mode When Farm Premium is employing Minimum or Tunnel Ventilation, the Hot Screen displays the conditions needed to enter Natural Mode. NOTE: The Between Temp parameters can change based on the wind speed. Refer to Minimum Wind Speed for Tunnel Temp, page 60.
Feed Scale enables mixing different types of feeds from (up to) four different silos. The user fills each bin with the required feed type and sets the mixture rations and quantities in Farm Premium. The augers then distribute the feed as defined.
Page 63
3636 5. Define: o Day: Define the days at which the feed per bird changes. Farm Premium calculates a feed curve based on these days. You can define the days as negative days. Enter the day number and press +/-.
The number does not need to be exact. In the following feed runs, Farm Premium will correct the amount entered. o Optimizer: This parameter sets the unit's sensitivity to signal noise (caused by a variety of factors).
7. Set the Feed Alarms (page 71). If you have installed load cells and connected silo scales to your Farm Premium, it automatically maintains feed inventory, including delivery dates and feed consumption data. You can monitor your fill system and...
Page 70
Overtime Alarm shuts down the augers and feeders, regardless of the other alarm's setting. Auger Empty Alarm Condition Detection Delay (sec.): Farm Premium sends an alarm when the current goes to the • level set in the following parameter after this delay.
Potentiometer Alarm 5.5.2 P RIORITIZING LARMS Farm Premium 5.16 enables prioritizing alarms. When enabled: ventilation-related alarms are defined as critical. The main alarm relay will transmit these • alarms to the device wired to the relay (for example, a dialer).
The Farm Premium has six options besides controller failure or power off to activate the fail-safe relay. Apply the additional settings by using the '+/-' key: High/Low Temperature: Select to trigger fail-safe when the temperature is exceptionally • high/low. Low/High Static Pressure: Select to trigger fail-safe when the static pressure is exceptionally •...
Munters Farm Thermo-5 is a five stage digital thermostat that works in conjunction with Farm Premium Controllers or as a stand-alone unit. When wired to the Farm Premium, you can use the Farm Premium to set the Farm Thermo-5's stage activation temperatures (which is easier than setting the temperatures on the Farm Thermo-5 screen).
Notes: o Farm Premium does not store these temperatures; Farm Thermo-5 does. If you connect the Farm Premium to a different Farm Thermo-5 unit, you must re-enter the temperature curve. o If you previously defined the temperature curve in the Farm Thermo-5, Farm Premium retrieves the data and you can edit the data in this screen.
7.7 Heaters The Farm Premium maintains daily total run times of each heater. The table fills several screens; to view the off screen data, use the arrow keys to scroll. The data is in hours:minutes format. 7.8 Radiant Heaters The Farm Premium maintains daily total run times of each radiant heater, including separate data for low level and high-level heaters.
8 Test Menu The Test Menu screen shows internal information in order to verify that the Farm Premium is operating correctly. Moreover, it can help find broken wires or any other problems related to it. Switches & Relays, page 89 •...
• Note that the alarm relay is powered for the ‘NO ALARM’ condition to provide automatic Power Fail Alarm in case of power failure to the Farm Premium. That is, the Normally Open side is closed during NO ALARM. ALARM TEST...
8.7 Communication This menu facilitates testing on communication networks. A multiplexer in loop back mode is used to test the communication. The Farm Premium follows its' own communication to check for failed hardware. Follow the instructions displayed on the screen.
Figure 20: Pigs Service Screen 9.1 Temperature Calibration The Farm Premium temperature sensors are typically accurate to approximately 0.5º F within the range of temperatures for poultry production. Calibrate them in this menu by adding/subtracting a constant correction factor to each sensor. Adjust the sensor of your choice with the left/right arrow keys.
1. Obtain an accurate reference sensors and a pail of water at the approximate required temperature. 2. Stir the reference sensor together with the Farm Premium sensor vigorously in the bucket of water. Keep hands off the sensor itself, so that it responds accurately to the water temperature. Stirring is necessary to preclude stratification within the bucket of water.
The Static Pressure sensor is factory calibrated. Only calibrate the sensor if you have reason to believe that they are producing inaccurate results. NOTE: Run Farm Premium for a few hours so that the temperature in the box becomes stable and only then calibrate. CAUTION DO NOT blow the air into the hose to see of the pressure changes! The sensor is sensitive and blowing air can cause irreparable damage.
9.6 Feed Calibration Farm Premium can use silo scales or less expensive digital monitoring devices to keep track of your feed. This menu calibrates the digital monitoring devices. 1. Select the feed counting method. Your digital monitoring device may generate a dry contact pulse for each quantity of feed, or it may simply indicate that the feed is running.
Enter relays according to equipment installation (I/O list of technician) using up/down arrow • keys. If you have installed Current Sense relays, Farm Premium defines them automatically. Current • sense relays transmit to the user’s PC the amount of the current being passed to the relay and send alarms when the current is too low or too high.
Install analog input cards. This screen enables the user to install the analog sensors. The Farm Premium regards temperature, humidity, and CO2 sensors and circuit breaker as analog sensors. These sensors measure a continuous range rather than just on or off.
< None Enter sensors wired to each input (setup according to technician) • Farm Premium automatically numbers the sensors according to their function. • o You cannot define more than the permitted number of any particular sensor. For example, you can define one function as Cool Pad Water Meter, not two.
• Wind Direction (Natural programming only) • If you map a curtain or vent to a potentiometer, the Farm Premium controller uses that method (and not time). NOTE: After defining the method used, define the opening levels in Vent & Curtain Levels, page 41.
Page 112
Enter the number of seconds to open and close from limit to limit for each of the Vents and Curtains in your installation. The Farm Premium then calculates the percentage of open and closed time and adjusts the static pressure methods accordingly.
In many installations the backup system, such as Munters' FBU-27, may have opened the air sources. When the Farm Premium takes over control again, the air inlets are incorrectly positioned. The calibration at power up feature synchronizes the actual position and the controller.
Farm Light Dimmers connected via a communication card. NOTE: If the Farm Premium Controller has an analog output card, you can map multiple RLD units using an output card and a communication card. However, the Farm Premium software...
12 Appendix B: Farm Premium Layers This section details functions specific to the Farm Premium Layers mode. Layers Main Screen • Layers Vent and Curtain Levels • NOTE: Layers Mode supports 20 water meters. 12.1 Layers Main Screen SENSORS AV. TEMP.
Delay for Compensation (minutes): As the temperature sensors record changes in • temperature, Farm Premium waits this amount of time before changing the inlet position. Default: 5 minutes Maximum Compensation Opening: Inlet opening does not differentiate from the set level •...
13 Appendix C: Farm Premium Breeders • Egg Room Setup • Egg Room Water and Feed • Egg Belt Runtime • Egg Room Hot Screen • Egg Room History 13.1 Egg Room Setup The following procedures details the steps required to set up the Egg Room functions.
Run Time (sec). Feed Line 1 Up Feed Line 1 Down Feed Line 2 Up Feed Line 2 Down Additional points: • In Breeder Mode, Farm Premium supports up to: 10 feeders • Four water lines • Four augers •...
During feed distribution, each silo has a mechanical arm that disconnects at the end of a feed cycle, preventing further distribution. When this disconnect happens, a signal is sent from the arm to the silo, informing the latter that it must be refilled. Farm Premium enables recording these signals in the Events History.
12 months of the delivery of the defective product. Munters has thirty days from the date of receipt in which to take action, and has the right to examine the product at the customer’s premises or at its own plant (carriage cost to be borne by the customer).
Page 133
The use of non-original spare parts or incorrect assembly exonerates the manufacturer from all liability. Requests for technical assistance and spare parts can be made directly to the nearest Munters office. A full list of contact details can be found on the back page of this manual.
Page 134
Munters Brasil Industria e Comercio Ltda, Phone +55 41 3317 5050, Canada Munters Corporation Lansing, Phone +1 517 676 7070, Munters Air Treatment Equipment (Beijing) Co. Ltd, Phone +86 10 80 418 000, Munters A/S, Phone China Denmark +45 9862 3311,...
Need help?
Do you have a question about the Farm Premium and is the answer not in the manual?
Questions and answers