For EN50131- 1 compliant installations, the following programming options shall be set as described. Supervision Heart-
beat (required for ATS4 and ATS5):
NOTE: The compatible receiver at ARC location shall have the supervision window programmed for 1800s (ATS4) or 180s
(ATS5) for the primary communications path, which can be Ethernet receiver 1 or cellular receiver 1, depending on
the product being installed.
[851][107]
Set to 0087h (135s Heartbeat) for Ethernet Receiver 1
l
[851][207]
Set to 0087h (135s Heartbeat) for Cellular Receiver 1
l
[851][100]
Options 1 and 2 shall be enabled if using Ethernet Receiver 1 as the primary path
l
[851][200]
Options 1 and 2 shall be enabled if using Cellular Receiver 1 as the primary path
l
Configuration of communication paths (all ATS classes)
[300][001]
select option 02 for auto routing (this will allow transmission of the events over all available communication
l
paths in the system)
[380]
enable option 5 (YES) for parallel transmission over all available communication paths (if redundant con-
l
figuration is desired)
[382]
enable option 5 (YES) to enable Alternate communicator
l
[384]
enable the desired back-up configuration (receiver 2 back-up for receiver 1 or receiver 3 back-up for receiver 1).
l

EN50131-1 Installation Requirements