Original installa�on and opera�on manual
Code
Description / explanation
Time drain ON
Condensate drain, solenoid valve activation
Ton
time.
0 = BEKOMAT
Time drain OFF
Toff
Condensate drain, solenoid valve pause
time.
Dryer Remote Control
LOCAL = local START-STOP mode
REMOTE = remote START-STOP via digital
DrC
input signal
MODBUS = remote START-STOP via
Modbus RTU.
High Dew Point Alarm
HdA
Threshold temperature of Warning W2
High Dew Point Delay
Hdd
Delay time of triggering of Warning W2
High Dew Point alarm STOP
Behaviour of device during normal running
status with Warning W2 active
HdS
NO = device doesn't stops
YES = device stops
Service setting
SrV
Setting of maintenance timer
(*1)
0,0 = timer disabled
Units
ScL
°C = temperature in °C and pressure in bar
°F = temperature in °F and pressure in psi
(*1) With advanced parameter PSPR = YES, the parameter SrV can be modified only after typing the security
PIN.
80 | 120
drain installed
®
Value
Accuracy
range
0 ... 20
1
seconds
0 ... 20
1
minutes
LOCAL,
REMOTE,
-
MODBUS
0,0 ... 25,0 °C
or
0,1
32,0 ...
77,0 °F
1 ... 20
1
minutes
NO, YES
-
0,0 ... 12,0
0,1
(x 1000)
hours
°C, °F
-
DRYPOINT
®
RA III
Default
value
0
1
LOCAL
20,0 °C
or
68,0 °F
15
NO
8,0
°C