Beko DRYPOINT RA III 1080 Translation Of Original Installation And Operation Manual page 113

Compressed air refrigeration dryer
Table of Contents

Advertisement

DRYPOINT
®
RA III
ALARM code – Text
A11 – Low Differential Pressure
Trigger: ∆p < 2,5 bar(g)
Reset: ∆p ≥ 2,5 bar(g)
Delay: (*2)
A12 – High Evaporating Pressure
Trigger: LP > 4,8 bar(g)
Reset: LP ≤ 4,8 bar(g)
Delay: (*3)
A13 – Low Condensing Pressure
Trigger: variable
Reset: variable
Delay: (*3)
A14 – Reversed Phases
Trigger: DI7 open
Reset: DI7 closed
Delay: (*4)
A19 - Fan
Trigger: DI3 open
Reset: DI3 closed
Delay: none
A E 1001 – Communication lost
Trigger: cable HMI disconnected
Reset: cable HMI connected
Delay: 5 seconds
(*2) 15 minutes at device start-up, 60 seconds during normal operation
(*3) 15 minutes at device start-up, 600 seconds during normal operation
(*4) 0 seconds at device start-up, 2 seconds during normal operation
Cause
Transducers BHP and BLP, low
differential pressure between
values HP and LP
Transducer BLP, the evaporating
pressure of the refrigerant fluid is
too high.
Transducer BHP, the condensing
pressure of the refrigerant fluid is
too low.
Relay RPP, power phases L1, L2,
L3 are connected to the device
with the uncorrect phase
sequence.
Missing power phase.
The internal heat protection of
cooling fan has triggered.
The circuit breaker QV1 has
triggered.
Communication broken between
User Interface and Electronic
Control Unit
Original installa�on and opera�on manual
Action
Refer to section "16.2 Specific
malfunctions" on page 114,
"Transducers BHP and BLP, low
differential pressure between
values HP and LP".
Refer to section "16.2 Specific
malfunctions" on page 114,
"Transducer BLP, evaporating
pressure of refrigerant fluid too
high".
Refer to section "16.2 Specific
malfunctions" on page 114,
"Transducer BHP, condensing
pressure of refrigerant fluid too
low".
Restore the correct phase
sequence
Connect the missing phase
Wait 30 minutes to cool down
the motor then check carefully
the operation of cooling fan.
Restore the circuit breaker QV1
then check carefully the
operation of cooling fan, models
RA 2400 / 3000
Check the integrity of HMI
connection cable
113 | 120