STANDBY – RUNNING digital output
NOTE
Illustration
52 | 120
STANDBY – RUNNING digital output failure
The STANDBY – RUNNING contact is a potential-free NO contact. Using the
contact with unsuitable voltages and currents will cause its failure.
Contact rating current 4 A @ 250 Vac
Connection work
Description / explanation
1. Guide a two-wires signal cable through
the arranged rubber grommet on the
product.
2. Product side: connect the cable to the
connector M4 [RL4] DRYER ON of
Electronic Control Unit.
3. Plant side: connect the cable to the
supervisory system of the plant.
4. Make sure that power cable is free of
mechanical stress and mechanically
protected.
DRYPOINT
®
RA III