Delayed starting function
The device is provided of a delayed start function to avoid too frequent start/stop
cycles which could damage the refrigerant compressor. The starting delay occurs:
•
After the booting of User Interface consequently to the switch ON of the
device.
•
Starting delay: 300 seconds.
•
After stopping the device using the START-STOP button and an immediate
restart attempt. Starting delay: 180 seconds.
Description / explanation
Stopping the device
1. Press and hold the START-STOP
button [1] for 3 seconds.
The device stops.
The User Interface shows STANDBY.
Starting the device
1. Press and hold the START-STOP
button [1] for 3 seconds.
The device starts.
The User Interface shows ON and the
dew point temperature.