N7 IECEx Type n
Certificate
Standards
Markings
Special Condition for Safe Use (X):
If fitted with a 90 V transient suppressor, the equipment is not
capable of withstanding the 500 V electrical strength test as defined
in Clause 6.5.1 of IEC 60079-15:2010. This must be taken into account
during installation.
11.1.5  Brazil
E2 Brazil Flameproof
Certificate
Standards
Markings
Temperature class
T6
T5
T4
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1
mm thick that forms a boundary between EPL Ga (process
connection) and EPL Gb (all other parts of the equipment).
The model code and datasheet are to be consulted for details
of the diaphragm material. Installation, maintenance, and
use shall take into account the environmental conditions to
which the diaphragm will be subjected. The manufacturer's
instructions for maintenance shall be followed in detail to
assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic
build-up on painted surfaces, and only clean the painted
surfaces with a damp cloth. If paint is ordered through
Quick Start Guide
IECEx BAS 08.0026X
IEC 60079-0:2011, IEC 60079-15:2010
Ex nA IIC T5 Gc, (–40 °C ≤T
UL-BR 15.0393X
ABNT NBR IEC 60079-0:2013, ABNT NBR IEC
60079-1:2016, ABNT NBR IEC 60079-26:2016
Ex db IIC T6...T4 Ga/Gb, T6 (–60 °C ≤ T
(–60 °C ≤ T
≤ +80 °C), IP66
a
Ambient temperature
-60 °C to +70 °C
-60 °C to +80 °C
-60 °C to +80 °C
Quick Start Guide
≤ +70 °C)
a
≤ +70 °C), T5/T4
a
Process connection
temperature
–60 °C to +70 °C
–60 °C to +80 °C
–60 °C to +120 °C
47