January 2024
Procedure
1. Expand the Conditioning Orifice Plate category.
2. Select 405C/3051SFC.
3. Enter the measured Meter Tube Diameter (pipe ID) at a
reference temperature. If the meter tube diameter cannot be
measured, select a Nominal Pipe Size and Pipe Schedule to
input an estimated value for the meter tube diameter (English
units only).
4. If necessary, edit the Meter Tube Material.
5. Enter the Line Size and select the Beta of the conditioning
orifice plate. The required primary element sizing parameters
will be different depending on what primary element was
selected.
6. If necessary, select a primary element Material from the
dropdown menu.
7. Select Next > to advance to the Save/Send Configuration tab.
Note
To be in compliance with appropriate national or international
standards, beta ratios and differential producer diameters
should be within the limits as listed in the applicable
standards. The Engineering Assistant software will alert the
user if a primary element value exceeds these limits, but will
allow the user to proceed with the flow configuration.
7.7 
Save/send configuration
The Save/Send Configuration tab shown in
to verify, save, and send the configuration information to the
transmitter with the fully compensated mass and energy flow feature
board.
Quick Start Guide
Quick Start Guide
Figure 7-7
allows you
29