Quick Start Guide
7.4 
Select fluid for database liquid/gas
The Fluid Selection tab shown in
the process fluid.
Figure 7-4: Fluid Selection Tab
Note
The following example will show a flow configuration for the
database gas air used with a Rosemount 405C Conditioning Orifice
Plate as the primary element. The procedure to set up any other
fluid with any other primary element will be similar to this example.
Natural gases, custom liquids, and custom gases require additional
steps during the configuration. See the Rosemount 3051SMV
Reference Manual
Procedure
1. Engineering Assistant may open to the Preferences tab. Using
the tabs at the top of the screen, navigate to the Fluid
Selection tab.
2. Expand the Gas category (click on the + icon).
3. Expand the Database Gas category.
4. Select Air from the list of database fluids.
5. Enter the Nominal Operating Pressure, select the Enter or Tab
key.
6. Enter the Nominal Operating Temperature, select the Enter
or Tab key. Engineering Assistant will automatically fill in
suggested operating ranges, as shown in
values may be edited as needed by the user.
26
Figure 7-4
for more information.
January 2024
allows the user to choose
Figure
7-4. These
Emerson.com/Rosemount