Emerson Rosemount 3051S Series Quick Start Manual page 16

Flow meter multivariable transmitters
Hide thumbs Also See for Rosemount 3051S Series:
Table of Contents

Advertisement

Quick Start Guide
Figure 5-1: Transmitter Wiring
Note
Installation of the transient protection terminal block does not
provide transient protection unless the Rosemount 3051SMV
housing is properly grounded.
5.1 
Conduit electrical connector wiring (option GE or
GM)
For Rosemount 3051SMV with conduit electrical connectors GE or
GM, refer to the cordset manufacturer's installation instructions
for wiring details. For FM Intrinsically Safe, Division 2 hazardous
locations, install in accordance with Rosemount drawing 03151-1009
to maintain outdoor rating (NEMA
3051SMV
5.2 
Power supply
The Dc power supply should provide power with less than two
percent ripple. The total resistance load is the sum of the resistance
of the signal leads and the load resistance of the controller, indicator,
intrinsic safety barriers, and related components.
16
Without optional process
temperature connection
 
A. Power supply
Reference
Manual.
With optional process temperature
connection
A
RL ≥ 250Ω
 
4X and IP66). See the Rosemount
®
January 2024
RL ≥ 250Ω
Emerson.com/Rosemount
A