When any trouble with UPS, please check the problem refer to the table below first. If the
problem cannot be solved, please contact local supplier.

6.1 LCD Warning and Fault Code

Fault
code
Description
01
UPS start up not success
Internal DC BUS over-voltage
02
protection
Internal DC BUS under-
03
voltage protection
10
UPS Output Short-Circuit
22
UPS Overload
23
UPS Over Temperature
29
UPS Input rectifier protection
57
Battery UN-connected
59
Charger Fail
60
EPO activated
Battery Icon Flashing
UPS not working normal line mode ,
With normal mains input
Backup time is not as long as expected
UPS do not turn ON
after pressing ON/OFF button

Chapter 6 Trouble shooting

Battery Low
UPS Internal failure, Contact distributor for service
Half-wave rectifier load(hair dryer , half-wave solenoid valve , energy re-
generated type load (motor, huge transformer, capacitor with residue charge,
remove this kind of load and turn on the UPS again.
Over mains voltage, turn on the UPS again.
UPS Internal failure, Contact distributor for service
Battery Low or overload
UPS Internal failure, Contact distributor for service
Remove short-circuit equipment from UPS
Reduce loading capacity below UPS rating
Make sure UPS should work in ambient of -10-45
can't meet this spec. Try reducing loading
Check ventilation inlet of the UPS ON from panel and outlet on the rear panel
is not blocked
UPS Internal failure, Contact distributor for service
Low input voltage and overload
UPS Internal failure, Contact distributor for service
Check battery input wiring and battery cutoff device such as circuit breaker etc.
UPS Internal failure, Contact distributor for service
Reset the External EPO switch,if no EPO switch install, turn off EPO function
via the operating panel
Battery not connected or battery low
Charger failure, Contact distributor for service
Make sure Input circuit breaker is ON
Turn on the UPS via ON/OFF button
Battery low, recharge the battery long enough time
Overload, reduce the loading
Battery aged, Contact distributor for service
Press the ON/OFF button long enough time, 3seconds , and hear a buzzer
beep for acknowledging the correct TURN ON operation
Battery low or not connected
UPS Internal failure, Contact distributor for service
Possible cause and solution
32
o
C, if the ambient temperature