02: Output frequency
Display
03: Auto turn on upon mains power on
⚫
Display
Value
Parameter Item: Output frequency
000: auto adaptive, the UPS will automatically detect the
mains frequency to determined it output frequency
when it wake up by mains power on
050: Fixed 50Hz rated frequency
060: Fixed 60Hz rated frequency
Use "UP Page" or "Down Page" Button to find desired
voltage value , then Use "ENTER" button to activate the
value, once the value is active, there is "Hz" icon shown
behind the value
Example:
Value
Auto turn ON Function setting
ON: Enable auto turn on function, when the UPS wake by AC
mains apply , the UPS will automatically turn on and run in line
mode
OFF:Disable auto turn on function, the UPS will stay on
standby mode /bypass mode until manual turn on operation
Use "UP Page" or "Down Page" Button to find desired voltage
value , then Use "ENTER" button to activate the value, once the
value is active, there is "OUT" icon shown above the value
23