Ablerex ARES PLUS-ECO 1K User Manual page 15

208/220/230/240v online ups
Hide thumbs Also See for ARES PLUS-ECO 1K:
Table of Contents

Advertisement

Nominal Battery voltage
Model
1K
2K
3K
The external battery bank must be in accordance with UPS rated battery voltage, find UPS rated
battery voltage in model plant on the rear panel of the product
Standard external battery module has an extending port, which is used to extend external
battery capacity, just plug battery cable to the extending port of adjacent model and battery
cable of the last module connect to the UPS battery connector on the rear panel of the UPS,
For non-standards battery module, the external battery bank must have a cut-off device, like
circuit breaker or switch with fuses.
TURN OFF the cut-off device, make sure no harmful voltage can be touched on the connector.
Use only battery bank of correct voltage, check the product rating label for correct information.
Choose Wire with sufficient current rated, prepared well the terminal
CHECK THE POLARITY of battery bank, fix wires of correct polarity to the battery bank with
proper color and clear label for distinguish the polarity.
Securely Plug / Fix the other end of the cable to UPS
Check the polarity of the wiring and fastness of the connection
Powered the UPS by turning on the cutoff device
This UPS may work with a maximum of 4 extension battery cabinets.
Nominal Battery Voltage
24V
48V
72V
Rated Battery
Current
45A
45A
45A
15
Recommended Wiring cable
for non-standard EBC
>10AWG/6mm
>10AWG/6mm
>10AWG/6mm
2
2
2

Advertisement

Table of Contents
loading

Table of Contents