Emerson Rosemount 1066 Quick Start Manual page 21

Single channel transmitter
Hide thumbs Also See for Rosemount 1066:

Advertisement

February 2024
3. To ground the transmitter, attach the shield to TB2-3.
Note
For optimum electromagnetic interference (EMI) and radio
frequency interference (RFI) immunity, shield the power
supply/output cable and enclose it in an earth-grounded metal
conduit. Do not run power supply/signal wiring in the same
conduit or cable tray with loop power lines. Keep power
supply/signal wiring at least 6 ft. (2 m) away from heavy
electrical equipment.
Figure 2-4
and control pH and chlorine levels in drinking water. The figure also
shows three ways in which Fieldbus communication can be used to
read process variables and configure the transmitter.
Figure 2-4: Configuring Rosemount 1066P Transmitter with
F
OUNDATION
A. DeltaV configurator and host
B. Fieldbus technician configurator
C. Other host
D. Power supply
E. Filter
F. Terminator
G. Process line
H. pH sensor
I. Terminator
Quick Start Guide
shows the Rosemount 1066PFF being used to measure
Fieldbus
Quick Start Guide
21