8.2 Valve-specific basic settings

For actuator commissioning, select actuator mode Commissioning. To activate Commis-
sioning mode, user level Maintenance is required. Please refer to the separate firmware
description for the listing and explanation of the different user levels available. Then, the
message appears as shown in figure 8.1 is displayed:
Acknowledgement via ENTER push button/key generates the screen as shown in 8.2:
At this level, you may either select the actuator Commissioning menu or the actuator Pa-
rameters menu. In a first step, the valve specific parameters can be checked and adapted
if required such as: final positions, closing direction, type of seating and torques.
38
Figure 8.1: Display indication 1
Figure 8.2: Display indication 2
8. COMMISSIONING