4.2.30 Reset selection/disconnected PU detection/PU stop
selection (Pr. 75)
Pr. 75 "reset selection/disconnected PU detection/PU stop selection"
You can select the reset input acceptance, operation panel (FR-PA02
PU04) connector disconnection detection function and PU stop function.
• Reset selection
• PU disconnection detection: When it is detected that the operation panel (FR-PA02
• PU stop selection
Parameter
Number
75
<Setting>
Pr. 75
Reset Selection
Setting
0
Reset input normally enabled.
Reset input enabled only when the
1
protective function is activated.
2
Reset input normally enabled.
Reset input enabled only when the
3
protective function is activated.
14
Reset input normally enabled.
Reset input enabled only when the
15
protective function is activated.
16
Reset input normally enabled.
Reset input enabled only when the
17
protective function is activated.
: You can select the reset function input timing.
)/PU (FR-PU04) is disconnected from the inverter for
02
more than 1s, the inverter outputs an alarm code
(E.PUE) and comes to an alarm stop.
: When an alarm occurs in any operation mode, you can
stop the inverter from the PU by pressing the
Factory
Setting Range
Setting
14
0 to 3, 14 to 17
PU Disconnection
Detection
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
110
PARAMETERS
) or PU (FR-
-02
STOP
key.
RESET
PU Stop
Selection
Pressing the
STOP
key
RESET
decelerates the
inverter to a stop
only in the PU
operation mode.
Pressing the
STOP
key
RESET
decelerates the
inverter to a stop
in any of the PU,
external and
communication
operation
modes.
-