Parameter Number
117
118
119
120
121
122*
123
124
342
*
When making communication, set any value other than 0 in Pr. 122 "communication
check time interval".
<Setting>
To make communication between the personal computer and inverter, the
communication specifications must be set to the inverter initially. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
Note: After making the initial setting of the parameters, always reset the inverter. After
you have changed the communication-related parameters, communication
cannot be made until the inverter is reset.
Parameter
Name
Number
Communication
117
station number
Communication
118
speed
119
Stop bit length
Parity check
120
presence/
absence
Number of
121
communication
retries
Factory Setting
0
192
1
2
1
9999
9999
1
0
Setting
Station number specified for communication from the
PU connector.
0 to 31
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
48
4800bps
96
9600bps
192
19200bps
0
Stop bit length 1 bit
8 bits
1
Stop bit length 2 bits
10 Stop bit length 1 bit
7 bits
11 Stop bit length 2 bits
0
Absent
1
Odd parity present
2
Even parity present
Set the permissible number of retries at occurrence of
a data receive error.
0 to 10
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an alarm
stop.
If a communication error occurs, the inverter will not
come to an alarm stop. At this time, the inverter can be
9999
coasted to a stop by MRS or RES input.
(65535)
During a communication error (H0 to H5), the minor fault
signal (LF) is switched on. Allocate the used terminal
with any of Pr. 190 to Pr. 192 (multi-function outputs).
125
PARAMETERS
Setting Range
0 to 31
48, 96, 192
Data length 8
Data length 7
0, 1, 2
0 to 10, 9999
0, 0.1 to 999.8 s, 9999
0 to 150, 9999
0, 1, 2
0, 1
Description
0, 1
10, 11
4