Mitsubishi Electric FR-E560 Series Instruction Manual page 214

Transistorized inverter
Table of Contents

Advertisement

Switching mode between the PU operation mode and network operation
mode (when used with a communication option)
You can switch operation between the PU operation and network operation from the operation
panel or parameter unit (FR-PU04) during starting up in the network operation mode.
Pr. 340
Setting
Pr. 79
PU or network
0
operation
1
PU operation
2
Network operation
External/PU combined
3
operation
External/PU combined
4
operation
6
Switch-over
10
7*
PU operation interlock
Operation mode switch-
8*
over by the external
signal
* When Pr. 79 = "7 or 8", the inverter operates in the same manner as when Pr. 340 =
"0". (The inverter will not operate in the network operation mode at powering on.)
Operation Mode
Mode at Power On or at Restoration
from Instantaneous Power Failure
Inverter operates in the network operation mode.
Operation mode can be switched between the PU
operation and the network operation.
Inverter operates in the PU operation mode.
Inverter operates in the network operation mode.
Input running frequency from the PU and the start
signal from outside.
Input running frequency from outside and the start
signal from the PU.
Inverter operates in the network operation mode.
Operation mode can be switched between the PU
operation and the network operation.
MRS signal ON..... Inverter operates in the
external operation mode.
(Operation mode can be
switched to the PU operation
mode by the parameter unit.)
MRS signal OFF... Inverter operates in the
external operation mode.
X16 signal ON ...... Inverter operates in the
external operation mode.
X16 signal OFF .... Inverter operates in the PU
operation mode.
204
APPENDIX