REMARKS
This function is invalid during jog operation and PID control operation.
Setting frequency is "0"
• Even when the remotely-set frequency is cleared by turning on the RL (clear)
signal after turn off (on) of both the RH and RM signals, the inverter operates at
the remotely-set frequency stored in the last operation if power is reapplied
before one minute has elapsed since turn off (on) of both the RH and RM signals
Remotely -set frequency
stored in the last operation
Output
frequency
(Hz)
Acceleration (RH)
Deceleration (RM)
Clear (RL)
Forward rotation (STF)
Power supply
• When the remotely-set frequency is cleared by turning on the RL (clear) signal
after turn off (on) of both the RH and RM signals, the inverter operates at the
frequency in the remotely-set frequency cleared state if power is reapplied after
one minute has elapsed since turn off (on) of both the RH and RM signals.
Remotely -set frequency
stored in the last operation
Output
frequency
(Hz)
Acceleration (RH)
Deceleration (RM)
Clear (RL)
Forward rotation (STF)
Power supply
When selecting this function, re-set the maximum frequency according to
the machine.
Within one minute
ON
OFF
ON
ON
ON
More than
one minute
ON
OFF
ON
ON
CAUTION
101
PARAMETERS
Remotely -set frequency
stored in the last operation
ON
ON
1 minute
Operation at a set
frequency of 0Hz
ON
ON
ON