3.3.5

Combined operation mode 2

When the running frequency is set from a potentiometer connected across terminals 2-5
(frequency setting potentiometer) and the start signal is provided by the
key of the operation panel. (FR-PA02
REV
Operation command:
Frequency setting:Externally connected frequency setting potentiometer or multi-speed
Step
Power on
Switch power on.
1
Operation mode
Refer to page 54 and set "4" in Pr. 79 "operation mode
selection".
2
The [PU] and [EXT] indications are lit.
Start
Press the
RUN
The [RUN] indication is lit to indicate forward rotation, or flickers to
3
indicate reverse rotation.
Acceleration → Constant speed
Slowly turn the potentiometer connected across terminals 2-5
(frequency setting potentiometer) fully clockwise.
4
The frequency shown on the display increases gradually to
60.00Hz.
Deceleration
Slowly turn the potentiometer connected across terminals 2-5
(frequency setting potentiometer) fully counterclockwise.
5
The frequency shown on the display decreases gradually to
0.00Hz.
The motor stops running.
Stop
STOP
Press the
RESET
The operation command indication RUN goes off.
6
<Reference> If other frequency is required at fully clockwise position, change Pr. 38
"frequency at 5V (10V) " setting. (Refer to page 91.)
key (or
FWD
RUN
command (multi-speed command has priority) Refer to page 76.
Description
key (or
/
REV
FWD
key.
OPERATION/CONTROL
) (Pr.79 = 4)
-02
/
key) of the operation panel (FR-PA02
REV
key) of the operation panel.
62
key or
FWD
RUN
)
-02
Image
ON
Flicker
RUN
FWD
REV
Hz
RUN
MON
PU
EXT
External potentiometer
External potentiometer
Hz
MON
PU
EXT
/