Mitsubishi Electric FR-E560 Series Instruction Manual page 36

Transistorized inverter
Table of Contents

Advertisement

2) Sink logic type
• In this logic, a signal switches on when a current flows out of the corresponding signal
input terminal.
Terminal SD is common to the contact input signals. Terminal SE is common to the
open collector output signals.
Current
STF
STR
SD
• Use terminal PC as a common terminal to prevent a malfunction caused by
undesirable current.
(Do not connect terminal SD of the inverter with terminal 0V of the external power
supply. When using terminals PC-SD as a 24VDC power supply, do not install the
power supply in parallel outside the inverter. Doing so may cause misoperation due to
undesirable current.)
R
R
AY40 type
transistor output
module
STF
1
2
STR
9
10
24VDC SD
Current flow
26
INSTALLATION AND WIRING
Inverter
RUN
SE
Inverter
24VDC
(SD)
PC
AX40
1
R
R
9
24VDC