Presence detector and motion detector 360° compact
Area I cut out
Areas I + II cut out
without push-on cover
Pull off push-on cover.
Using scissors, cut out push-on cover along the marked lines as required.
Push on push-on cover.
Alternatively, the detection field can also be limited by switching off individual
sensors (see Commissioning).
6.2

Commissioning

Insert battery into IR remote control
The necessary settings are carried out using the "installation engineer" IR remote
control (see Accessories).
If multiple devices are within the range of the IR remote control, then align it so
that only the device to be operated can receive the signals.
Inserting the battery
Obey the battery safety instructions.
Keep contacts of batteries and device free of grease.
Insert the supplied battery with correct polarity (see IR remote control imprint).
Button assignment of the "installation engineer" IR remote control
Taste
1 sŮ
30 s Ů, 2 min Ů, 5 min Ů, 30 min Ů
ũ
Pressing for longer than 10 seconds
Ê, Ŧ, ŧ, Ũ
0-1 hŮ
Dyn.Ů Pressing for longer than 10
seconds
PIR A, PIR B, PIR C, PIR A-C
Pressing for longer than 10 seconds
PIR A, PIR B, PIR C, PIR A-C
Pressing for less than 10 seconds
25%, 50%, 75%, 100%
Ū
Pressing for longer than 10 seconds
82593232
25.09.2023
Ø approx. 7.5 m
Ø approx. 12 m
Ø approx. 20 m
Funktion
Short-time operation
Set run-on time
Saving ambient brightness as brightness
threshold
Setting the brightness threshold
Setting individual run-on time
Switching on the dynamic run-on time
Switching off the PIR sensors
In the next 5 seconds, use the 25%, 50%,
75% and 100% buttons to set the sensit-
ivity of the appropriate PIR sensor
Setting the sensitivity
Switching on the Presence detector
device function