Presence detector and motion detector 360° compact
For an additional flush-mounted cable entry or surface-mounted cable entry,
break out the appropriate thin point (13) (see figure 8).
Fastening the connection box (1) through holes (11) (see figure 8).
Alternatively, the device can also be mounted on a 60 mm appliance box. The
screws are not included in the scope of delivery.
Connect device
Figure 10: Connection diagram, parallel circuit for expanding the detection field
Max. power cable length 100 m. This takes into account all the connecting cables
between the devices and lamps.
Do not connect more than five devices in parallel.
Connect all devices to the same phase conductor.
Set all the devices to the same device function (motion detector or presence de-
tector).
The connection in parallel does not increase maximum connected load.
Connect the sensor cover according to the connection diagram (see figure 9)
or switch the sensor covers according to the circuit diagram (see figure 10).
If multiple circuit breakers supply dangerous voltages to the device or load,
couple the circuit breakers or label them with a warning to ensure tripping.
82593232
Figure 9: Connection diagram, single device
25.09.2023