Solar pump drive
Hide thumbs Also See for CFW11:

Advertisement

Parameters Description
P1030
The system tries to control the motor speed accordingly to the Manual Speed Setpoint (P1051 or AI2). With limited
0
radiation, the system controls the DC bus voltage, causing the pump to run at maximum speed possible to reach
the Manual Speed Setpoint.
The system operates through the DC voltage control and when the solar radiation allows controlling the Output
1
Pressure. With limited radiation, the system controls the DC bus voltage, causing the pump to run at maximum
speed possible to reach the Pressure Setpoint.
The selection of Manual or Automatic Mode is made by DI5 (0=Manual / 1=Automatic). The DI5 must also be
2
programmed for this function, check the parameter P0267.
Disable the Pressure Control. The system controls the DC bus voltage, causing the pump to run at maximum speed
3
possible, limited to the maximum speed (P0134).
P1031 – Pressure Sensor Scale
Adjustable
0.0 to 300.0
Range:
Properties:
CFG
Access groups via HMI:
Description:
This parameter defines the full-scale value of the pressure sensor connected to the analog input 1 (AI1).
5.2.1 Pressure PID Controller
This group of parameters allows the user to configure the PID controller gains for the pressure control.
P1032 – Pressure PID Proportional Gain
Adjustable
0.000 to 32.000
Range:
Properties:
CFG
Access groups via HMI:
Description:
This parameter defines the proportional gain value of the PID controller for the pressure control.
P1033 – Pressure PID Integral Gain
Adjustable
0.00 to 320.00
Range:
Properties:
CFG
Access groups via HMI:
Description:
This parameter defines the integral gain value of the PID controller for the pressure control.
P1034 – Pressure PID Derivative Gain
Adjustable
0.000 to 32.000
Range:
Properties:
Access groups via HMI:
Description:
This parameter defines the derivative gain value of the PID controller for the pressure control.
Table 5.2 – Pressure Control Mode Options
SPLC
SPLC
SPLC
SPLC
Description
Application Default Setting:
Application Default Setting:
Application Default Setting:
Application Default Setting:
10.0
1.000
10.00
0.000
Solar Pump Drive | 26