Installation
3.2.2 T4 Model Frame E and F
For CFW11 frequency inverters from 380 to 480 V, model T4 Frame E and F, the following connection is
recommended:
Figure 3.4 – Connection diagram of the solar water pumping system for CFW11 T4
CFW11 T4 Model
Frame A and B
(series contact connection)
Frame C and D
(series contact connection)
Frame E and F
(series contact connection)
NOTE!
Take care to don't reverse the positive and negative voltage connections from the solar modules.
Do not open the contactors KC and/or KB with load.
NOTE!
The inputs/outputs connections may be different from what is indicated in this diagram,
depending on the needs of the application.
Table 3.4 – External pre-charge recommended components
Charge Contactor KC
CWB18 – 18A
CWB25 – 25A
CWB25 – 25A
Pre-Charge Resistor RC
60 Ohm / 150 J @ 0,3s
(RH50 – 60 Ohm)
40 Ohm / 1000 J @ 1s
(2X IRV200 – 20 Ohm)
40 Ohm / 7000 J @ 5s
(2X IRV200 – 20 Ohm)
By Pass Contactor KB
CWB9 ~ CWB18
(parallel contact connection)
CWB18 ~ CWB50
(parallel contact connection)
CWM50 ~ CWM250
(parallel contact connection)
Solar Pump Drive | 17