Item
Battery voltage
Issue 17 (2024-01-30)
Expected Result
● Equalized
charging
voltage: 14.16
V±0.1 V
● Float charging
voltage: 13.68
V±0.1 V
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Routine Maintenance
Measures
1. Check whether
the equalized
charging
voltage and
float charging
voltage of a
battery are
normal.
2. If the charging
voltage of a
battery exceeds
the
specifications
requirement,
perform a
complete
forcible
equalized
charging for
the battery,
and check
again whether
the voltage is
normal.
3. If the fault
persists,
contact
Huawei
technical
support.
Maintenance
Interval
Quarterly
86