Huawei UPS2000-A-1KTTS User Manual page 59

Hide thumbs Also See for UPS2000-A-1KTTS:
Table of Contents

Advertisement

UPS2000-A-(1 kVA-3 kVA)
User Manual
Figure 5-3 Setting parameters on the LCD
When the UPS is in standby mode or bypass mode, hold down the SELECT button
for 5s to enter UPS setting mode. In this case, all parameters can be set.
When the UPS is in normal mode or battery mode, hold down the SELECT button
for 5s to enable or disable the buzzer off function (BUZ), set the DHCP function
(DHP), and view the IP address (IP), subnet mask (SUB), and gateway (GAT).
In UPS setting mode, hold down the ON/MUTE button for more than 3s to go to
the previous option after a beep sound, and hold down the SELECT button for
more than 3s to go to the next option after a beep sound. When the UPS is in
setting mode, hold down the OFF/ENTER button for more than 3s to confirm the
setting.
Display
Issue 17 (2024-01-30)
Output voltage setting
Converter mode enable/disable
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Setting Control Panel
Setting
The output voltage can be set as
follows:
200: The output voltage is 200 V AC.
208: The output voltage is 208 V AC.
220: The output voltage is 220 V AC
(default).
230: The output voltage is 230 V AC.
240: The output voltage is 240 V AC.
52