Huawei UPS2000-A-1KTTS User Manual page 91

Hide thumbs Also See for UPS2000-A-1KTTS:
Table of Contents

Advertisement

UPS2000-A-(1 kVA-3 kVA)
User Manual
Item
Charge voltage of
battery string
Battery
temperature
sensor
measurement
accuracy
Issue 17 (2024-01-30)
Expected Result
● Equalized
voltage 14.16
V x Number of
batteries
(tolerance
±1%)
● Float voltage
13.68 V x
Number of
batteries
(tolerance
±1%)
The difference
between the
temperature
measured by the
temperature
sensor and the
temperature
displayed on the
LCD is less than
3°C.
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Routine Maintenance
Measures
1. If the voltage
drop between
the battery
string output
terminals and
the battery
input terminals
at the UPS side
is greater than
1% of the
battery string
voltage, check
whether the
cable between
the battery
string and the
UPS is
excessively
long, or the
cable diameter
is excessively
small.
2. Check whether
the equalized
charging
voltage and
float charging
voltage are
correctly set
for the UPS.
3. If the fault
persists,
contact
Huawei
technical
support.
1. Install the
temperature
sensor in the
correct
position.
2. Replace the
battery
temperature
sensor.
Maintenance
Interval
Monthly
Quarterly