Huawei UPS2000-A-1KTTS User Manual page 78

Hide thumbs Also See for UPS2000-A-1KTTS:
Table of Contents

Advertisement

UPS2000-A-(1 kVA-3 kVA)
User Manual
Alar
Caus
Nam
m ID
e ID
e
66
4
Outp
ut
overl
oad
158
1
On
bypa
ss
Issue 17 (2024-01-30)
Seve
Clear
Trigger
rity
ance
Condition
Mod
e
transfers
to no
output
mode.
Critic
This
The bypass
al
alarm
overload
must
exceeds the
be
time limit.
manu
ally
cleare
d.
Mino
The
The UPS
r
alarm
transfers to
is
bypass mode.
auto
matic
ally
cleare
d.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Impact on the
Solution
System
The UPS
Possible cause: The
transfers to no
load exceeds the rated
output.
load capacity of the
bypass.
Measure: Lower the
load or replace the
UPS with a larger-
capacity UPS.
The UPS
● Possible cause: The
transfers to
bypass mode.
● Measure: Check
● If an alarm is
● Possible cause: The
● Measure: Lower the
5 Setting Control Panel
inverter is not
started.
whether other
alarms are reported.
generated, clear the
alarm by referring
to the handling
procedure. If no
alarm is generated,
start the UPS
manually.
load exceeds the
rated load capacity
of the inverter.
load or replace the
UPS with a larger-
capacity UPS.
71