The minimum input voltage in bypass mode must be lower than the minimum
voltage allowed in ECO mode.
Display
Display
Issue 17 (2024-01-30)
Setting the minimum input voltage in bypass mode
Battery capacity setting
Discharge time limit setting
ECO mode enable/disable
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Setting Control Panel
Setting
You can adjust the minimum input
voltage in bypass mode using ▲ and
▼.
170–220: The voltage can be set from
170 V AC (default) to 220 V AC.
Setting
You can adjust and set the UPS battery
capacity using ▲ and ▼.
18–999: The capacity can be set from
18 Ah to 999 Ah. (The value is fixed at
9 Ah for the UPS with standard backup
time, and the default value is 18 Ah
for the UPS with long backup time.)
Setting
Set the discharge time limit:
0–999: The time can be set from 0
minutes to 999 minutes.
0: The backup time is not limited
(default).