UPS2000-A-(1 kVA-3 kVA)
User Manual
Routine maintenance items for batteries
Table 8-2 Routine maintenance items for batteries
Item
Battery alarm
Battery
appearance
Battery operating
temperature
Issue 17 (2024-01-30)
Expected Result
No battery alarm
is generated.
1. The surface is
clean and tidy
without stains.
2. The battery
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from acid
leakage.
5. Batteries are
not deformed
or bulged.
1. The ambient
battery
temperature is
25±5°C.
2. The battery
operating
temperature is
lower than
battery
temperature +
20°C.
3. Battery charge
and discharge
conditions
meet the
requirements
specified in the
battery
specifications.
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Routine Maintenance
Measures
Identify the cause
based on the
alarm
information.
If the battery
appearance is
abnormal, contact
Huawei technical
support.
1. Identify the
cause of the
abnormal
battery
operating
temperature.
2. If the fault
persists,
contact
Huawei
technical
support.
Maintenance
Interval
Monthly
Monthly
Monthly
83