UPS2000-A-(1 kVA-3 kVA)
User Manual
No.
4
5
6
7
Issue 17 (2024-01-30)
Item
Cable labels
Ground cable connection
Distances between cable
ties
Operating environment
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Acceptance Criterion
Labels are neatly attached to both ends of
each cable, and the information on the
labels is concise and understandable.
The ground cable is securely connected to
the equipment room ground bar. Measure
the resistance between the UPS ground
cable and the equipment room ground bar,
which must be less than 0.1 ohm.
Distances between cable ties are the same,
and no burr exists.
The inside and outside of the cabinet are
free from conductive dust or other foreign
matter.
43