Before installing your frequency input module in the FLEX I/O system, you
need to:
• calculate the power requirements of all modules in each FLEX I/O
system, and
• position the keyswitch on the terminal base.
This FLEX I/O module does not receive primary operational power
ATTENTION
from the backplane. 24V DC power must be applied to your module
before installation. If power is not applied, the module position may
appear to the adapter as an empty slot in your chassis.
The wiring of the terminal base unit is determined by the current draw
through the terminal base. Make certain that the current draw does not
exceed 10 A.