Normal Operation; Figure 13: Olct 700/710 Ir Software Flowchart - Teledyne 700 IR Series Instruction Manual

Infrared gas detector for combustible and co2 gases
Table of Contents

Advertisement

Normal Operation

PGM1 (3)
PGM1 (3)
PGM2 (10)
PGM2 (3)
View Sensor Status
Auto Time-Out
PGM1/2 (M)
PGM1/2 (3)
Model Type
Version X.XX
inc
Gas Type
Range XXX
Serial ID XX
AutoSpan @ XX
Last Cal XX Days
inc
Sensor Life XXX%
Gas Factor = X.XX
Act Counts = XXXX
Ref Counts = XXXX
mA Output = XX.XX
Voltage XX.X VDC
Temp = XX C
3.3
Normal Operation
In normal operation, the OLCT 700/710 Display continuously shows the current detector
reading, which will normally appear as "0". Once every 60 seconds the LED display will flash
the detector's measurement units and gas type (i.e. % LEL). If the detector is actively experiencing
any diagnostic faults, a "Fault Detected" message will flash on the display once every minute.
When the unit is in "Fault Detected" mode, PGM1 or PGM2 can be swiped to prompt the detector
to display the list of the active faults.
In normal operation, the 4-20mA current output corresponds with the present gas concentration
and full-scale range. The RS-485 Modbus™ serial output provides the current gas reading and
fault status on a continuous basis when polled.
Caution: Off-scale readings may indicate a flammable concentration of gas.
NP700IRIMEN
Revision E.0
INFRARED GAS DETECTOR FOR COMBUSTIBLE AND CO
Software Flowchart
Calibration Mode
(Auto Zero)
Calibration Mode
(Auto Span)
Set AutoSpan Level
AutoTime-out
PGM1/2 (M)
inc
PGM1/2 (3)
##
PGM2 (S)
PGM1 (S)
dec
inc
PGM1/2 (3)
Set Serial ID
Auto Time-Out
PGM1/2 (M)
PGM1/2 (3)
##
PGM2 (S)
PGM1 (S)
dec
PGM1/2 (3)
Restore Defaults
Auto Time-Out
LEGEND:
PGM1/2 (M)
PGM2 (10)
PGM1 - Program Switch Location #1
PGM2 - Program Switch Location #2
(S) - Momentary Swipe
Defaults Restored
(M) - Momentary hold of Magnet during text
(3) - 3 second hold from ">" prompt
(10) - 10 second hold from ">" prompt
Auto Time-out - 5 seconds
inc - Increase
dec - Decrease
X, XX, XXX - numeric values

Figure 13: OLCT 700/710 IR Software Flowchart

Set Gas Type & Range
Auto Time-Out
PGM1/2 (M)
PGM1/2 (3)
Type ##
PGM2 (S)
PGM1 (S)
dec
PGM1/2 (3)
Range ##
inc
PGM2 (S)
PGM1 (S)
dec
PGM1/2 (3)
Set Sensor Gain
Auto Time-Out
PGM1/2 (M)
PGM1/2 (3)
Setting Gain
scroll until the ">" appears, then release
700 IR Series
2
GASES
USER MANUAL
Set Gas Factor
Auto Time-Out
PGM1/2 (M)
PGM1/2 (3)
##
PGM2 (S)
PGM1 (S)
dec
PGM1/2 (3)
Signal Output Check
Auto Time-Out
PGM1/2 (M)
PGM1/2 (10)
Simulation
PGM1/2 (3)
19