700 IR Series
INFRARED GAS DETECTOR FOR COMBUSTIBLE AND CO
GASES
USER MANUAL
From the View Sensor Status text scroll, hold the magnet over PGM1 or PGM2 until the ""
prompt appears and continue to hold the magnet in place for an additional 3-4 seconds (until
the display starts to scroll "Status Is"). The display will scroll the complete list of detector status
parameters sequentially:
Sensor Model Type
The menu item appears as: "700 IR"
Current Software Version
The menu item appears as: "Version 1.XX"
Gas Type
The menu item appears as: "Gas Type = CH4"
Range of Detection
The menu item appears as: "Range XXX"
Serial ID Address
The menu item appears as: "Serial ID XX"
AutoSpan Level
The menu item appears as: "Auto Span Level XX"
Days From Last AutoSpan
The menu items appears as: "Last Cal XX days"
Remaining Sensor Life
The menu item appears as: "Sensor Life 100%"
Gas Factor
The menu item appears as: "Gas Factor = X.XX"
Raw Active Counts
The menu item appears as: "Active Counts XXXX"
Raw Reference Counts
The menu item appears as: "Reference Counts XXXX"
4-20mA Output
The menu item appears as: "mA Output X.XX mA"
Input Voltage Supply
The menu item appears as: "Voltage XX.X VDC"
Sensor Operating Temperature
The menu item appears as: "Temp XX C"
When the status list sequence is complete, the OLCT 700/710 will revert to the "View Sensor
Status" text scroll. The user can either: 1) review list again by executing another 3-4 second hold,
2) move to another menu item by executing a momentary hold over PGM1 or PGM2, or 3) return
to Normal Operation via automatic timeout of about 15 seconds (the display will scroll "View
Sensor Status" 4 times and then return to Normal Operation).
24
2
NP700IRIMEN
Revision E.0