4)
A good ground connection should be verified between the sensor's metal enclosure and
the junction box. If a good ground connection is not made, the sensor can be grounded to
the junction box using the sensor's external ground lug. Also verify a good ground
connection between the junction box and earth ground. Installer shall use ring terminal to
make connection to earth ground to be secured by screw and lock washer on sensor
housing. Caution: do not loosen or twist the protective earth conductor. An earth conductor
shall be mounted so that it is secured against loosening and twisting.
5)
Ensure the Housing Bottom is threaded tightly to the Intelligent Transmitter Module. The
locking setscrew (M3.5 x 0.6 6g6h Stainless Steel Allen set screw cup point with yield
strength of greater than 40,000 PSI, typical 80,000 PSI) should then be tightened down
to keep the Housing Bottom from being inadvertently removed or from becoming loose
under vibration. The locking setscrew ensures that Housing Bottom is only removable by
authorized personnel with the use of special tools. A M1.5 Allen Wrench is required. If
screw requires replacement, only an identical screw may be used.
6)
Removal of the Housing Bottom violates the Ex d protection method and hence power must
be removed from the detector prior its safe removal.
7)
Proper precautions should be taken during installation and maintenance to avoid the build-
up of static charge on the plastic components of the detector. These include the splashguard
and splashguard adapter.
8)
When used in ATEX zone, OLCT 700 shall be attached to increased safety certified junction
box only.
9)
The sensor shall be installed on a metallic grounded structure such as the final assembly
assures that sensor enclosure is bonded to ground.
10) Proper precautions shall be taken during installation, operation, maintenance and service
of the product in order to avoid the build-up of static charges on the plastic splashguard.
11) The equipment manufacturer shall be contacted for information on the dimensions of the
flameproof joints.
12) The screws holding down the retaining plate are special fasteners of type: stainless steel,
Philips pan-head machine screws, M3 x 0,5 6g having yield strength greater than 40000
PSI.
2.2

Functional Safety (SIL 2)

Refer to safety user manual NP700IRSMEN
2.3

Detector Placement

Selection of detector location is critical to the overall safe performance of the product. Five factors
play an important role in selection of detector locations:
(1) Density of the gas to be detected
(2) Most probable leak sources within the industrial process
(3) Ventilation or prevailing wind conditions
(4) Personnel exposure.
8
2
NP700IRIMEN
Revision E.0