AWG
Wire Dia.
22
20
18
16
14
NOTE 1: Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.
NOTE 2: Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit or tray runs
are highly recommended in these cases.
NOTE 3: The supply of power should be from an isolated source with over-current protection as
stipulated in table.
2.7.1
Cable Preparation
NOTE : It is essential that the instructions provided by the manufacturer of the cable gland are
followed and the braid is correctly connected.
NP700IRIMEN
Revision E.0
INFRARED GAS DETECTOR FOR COMBUSTIBLE AND CO
Table 1: Wire Gauge vs. Distance
Cross Section
0,65 mm
0,32 mm²
0,8 mm
0,5 mm²
1,0 mm
0,8 mm²
1,3 mm
1,3 mm²
1,6 mm
2 mm²
1 - Remove the rubber pot and the two metal
washers (A)
700 IR Series
USER MANUAL
Over-Current
Meters/Feet
Protection
700/2080
1120/3350
1750/5250
2800/8400
4480/13440
2
GASES
3A
5A
7A
10A
20A
13