Customer
Supplied Wiring (In)
Power from and 4-20mA
out to Control Device
Modbus RS-485 to
Host Control Device
J1 Terminal
b) Observing correct polarity, terminate the 3-conductor 4-20mA field wiring (+, -, mA) to the
detector assembly wiring in accordance with the detail shown in Figure 10.
NOTE: If the 4-20mA output is not being used, the Green wire from the ITM
to the Black wire at the (-) terminal on the Transient Protection Module to ensure RS-485
communication is not disrupted by a 4-20mA Fault.
c) If applicable, terminate the RS-485 serial wiring. Use the second plug (Out) as termination
point on the customer side to facilitate a continuous RS-485 serial loop.
The RS-485 (if applicable) requires 24 gauge, two conductor, shielded, twisted pair cable
between detector and host controller. General Cable Commodore part number
ZO16P0022189 is recommended.
NOTE: Install a 120 ohm resistor across A & B terminals on the last detector in the serial loop.
d) Screw the cover firmly and loosen the locking screw until it reaches the cover.
Locking screw
NP700IRIMEN
Revision E.0
INFRARED GAS DETECTOR FOR COMBUSTIBLE AND CO
Explosion
Proof
Junction Box
(+)
(-)
mA
A(+)
B(-)
Wiring to
Sensor Assembly
Figure 10: Detector Wire Connections
700 IR Series
USER MANUAL
Customer
Supplied Wiring
(Out to next Device)
(+)
(-)
mA
A(+)
B(-)
Modbus RS-485 to
next Device
Install a 100-250 Ohm
resistor if the 4-20mA
output is not used
must
be connected
2
GASES
15