Analog Outputs (Ao); Wiring The Analog Outputs - Emerson FloBoss 107 Instruction Manual

Flow manager
Table of Contents

Advertisement

4.7

Analog Outputs (AO)

4.7.1 Wiring the Analog Outputs

Issued Feb-07
Figure 4-7. Loop Output Power for the I/O Module
The analog outputs (AO) provide a 4 to 20 mA current source output for
powering analog loop devices. Analog outputs are analog signals the
FB107 generates to regulate equipment, such as control valves or any
device requiring analog control. The AO includes the power supply
connections. The analog outputs use a 12-bit D/A converter with default
A/D values of 0 and 3250 (0 to 100% EU values).
Note:
Select AO as the I/O Type for the selectable analog
output/discrete output when you configure it for use as an analog
output. Refer to Figure 4-5.
The analog output provided on the I/O connects as follows:
AO+ Positive
AO− Common
: Be aware that you can induce ground loops by tying commons
Note
from various I/O together.
Figure 4-8 shows wiring for the analog output.
Inputs/Outputs and RTD Input
FloBoss 107 Instruction Manual
INTERNALLY
POWERED
4-11