Emerson FloBoss 107 Instruction Manual page 53

Flow manager
Table of Contents

Advertisement

Line
1
System Power Input
Base Unit including
2
CPU and Backplane Isolated
Expansion Rack
3
Inputs/Outputs
4
5
COM Modules
6
7
MVS Module
8
MVS Transmitters
9
10
11
12
13
Total FloBoss and Field Side Power Requirements in Watts (Line 12 + Line 13)
14
Entered Values =
Calculated Values =
Calculated Power (mW) = Quantity * (V dc * mA) * Duty Cycle
Note: Base Unit = CPU, backplane, on-board communications, LEDs, and RTD input
Amps = Total Power divided by Input Voltage (Line 14)
Issued Feb-07
Table 3-2. Estimated Power Consumption
Nominal
12 or 24
Volts dc
Quantity
Non-Isolated
0 or 1
0 or 1
CPU I/O Assembly
0 or 1
I/O Modules
0 to 6
RS-232
0 or 1
RS-485
0 or 1
MVS
0 or 1
0, 1, 2,
Remote MVS
3, or 4
DVS
0 or 1
Total Field Side Power Consumption from Table 3-3 (Watts)
Total System Current draw on Power Source
Power Connections
FloBoss 107 Instruction Manual
Input
Nominal
Voltage
Current
(Volts dc)
(mA)
12
12
12
12
12
12
12
12
12
mW (Totals of Lines 2 through 9)
FloBoss Total in Watts (Line 10 ÷ 1000)
Calc
Duty
Power
Cycle
(mW)
30
100%
360 or 540
45
100%
0
100%
3
100%
15
100%
3
100%
3
100%
10
100%
15
100%
1
100%
3-5