FB3000 RTU Instruction Manual
D301851X012
November 2023
3.2.5

Software Configuration

Consult the FBxConnect online help for full details. What follows is an overview of the
steps:
1. From the Configure tab in FBxConnect, click I/O Setup > HART.
2. Select the HART channel you want to configure; there are four HART channels per
3. If this channel is an analog input, click the Configuration tab to configure the AI.
4. Specify whether this is a Primary or Secondary HART Master in the HART Master
5. Enable the Termination Resistor if required.
6. Choose the HART Comm Mode
7. Click Save. If you chose Multidrop, the HART menu creates a button for each of
8. Click on the Device button to configure the HART device on this channel.
66
module.
Type field
If you have a single HART device on the channel, select Point to Point.
If multiple devices are multi-dropped on the channel, select Multidrop and
specify the Number of Devices.
the devices.