  • Page 1 FB3000 RTU Power Supply Module and Chassis Field Installation Guide D301874X012 June 2021 FB3000 Remote Terminal Unit (RTU) Power Supply Module (3PWBLK) and Chassis (3CH08A) Field Installation Guide Remote Automation Solutions...
  • Page 2: System Training

    Our full-time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or email us at education@emerson.com.
  • Page 3: Removing A Power Module

    June 2021 Removing/Replacing the Power Supply Module The FB3000 supports up to two power supply modules (3PWBLK). If you have two power modules installed, you can remove either one of them – but not both – while the RTU is operating.
  • Page 4: Replacing A Power Module

    Performing this operation in a hazardous area could result in an explosion. The FB3000 supports both 12V and 24V power supplies. It accepts DC voltage from 10.5 to 30V; the amount of power required varies depending upon the options used.
  • Page 5 FB000 RTU Power Supply Module and Chassis Field Installation Guide D301874X012 June 2021 Removing/Replacing the Chassis The FB3000 supports two chassis versions: 3CHO8C and 3CHO8A. This procedure is the same regardless of chassis type. DANGER Switch the process this RTU controls over to whatever manual/backup system you have.
  • Page 6 FB000 RTU Power Supply Module and Chassis Field Installation Guide D301874X012 June 2021 Removing the Personality Module Going from left to right starting with the second slot in the chassis, remove the first Mixed I/O module (3MIX12) present by depressing the orange tabs at the top and bottom of the module, and slide it out.
  • Page 7 FB000 RTU Power Supply Module and Chassis Field Installation Guide D301874X012 June 2021 Removing Slot Covers At this point, your chassis should be empty. Use a #2 Phillips head screwdriver to unscrew the chassis from its mounting location, which could be the DIN rail mounting plate, a panel, or a wall.
  • Page 8 Replace any slot covers removed in step 9 and then tighten the captive fastening screws. Reinstall each of the power modules. See Removing/Replacing the Power Module for more information. Restore power to the FB3000 by re-connecting the power terminal blocks to the power modules. See Removing/Replacing the Power Module for more information.
  • Page 9 Back up data in the CPU. (See Chapter 5 of the FB3000 RTU Instruction Manual [D301851X012]) for details.) Remove power from the FB3000 by disconnecting the terminal blocks from the power modules. See Removing/Replacing the Power Module for more information.
  • Page 10 FB000 RTU Power Supply Module and Chassis Field Installation Guide D301874X012 June 2021 Remove each of the power modules. See Removing/Replacing the Power Module for more information. Remove I/O modules in slots 2, 3, 6, and 7. Remove personality modules in slots 2 and 7. Support the chassis as you use a #2 Phillips-head screwdriver to remove the four screws that secure the chassis to the wall, panel, or mounting plate.
  • Page 11 FB000 RTU Power Supply Module and Chassis Field Installation Guide D301874X012 June 2021...
  • Page 12 FB3000 RTU Power Supply Module and Chassis Field Installation Guide D301874X012 June 2021 For customer service and technical support, visit www.Emerson.com/SupportNet Global Headquarters, North America, and Latin America: Emerson Automation Solutions Remote Automation Solutions 6005 Rogerdale Road Houston, TX 77072 U.S.A.