ACS140 Basic Parameters

ACS140 has a large number of parameters. Of these, only the so called basic
parameters are initially visible.
Setting up only a few basic parameters is sufficient in applications where the
preprogrammed application macros of the ACS140 can provide all desired
functionality. For a full description of programmable features provided by the
ACS140, see "ACS140 Complete Parameter List" starting on page 39.
The following table lists the basic parameters.
S = Parameters can be modified only when the drive is stopped.
Code Name
Group 99
START-UP DATA
9902
APPLIC MACRO
Selects application macro.Sets parameter values to their default
values. Refer to "Application Macros" starting on page 29, for detailed
description of each macro.
0 =
FACTORY MACRO
1 =
ABB STANDARD
2 = 3-
WIRE
3 =
ALTERNATE
Default value: 0 (
9905
MOTOR NOM VOLT
Nominal motor voltage from motor rating plate. Range of this
parameter depends on the type of the ACS140 (200/400 V unit).
Selection for 200 V units:
200, 208, 220, 230, 240 V
Default value for 200 V unit: 230 V
Default value for 400 V unit: 400 V
9906
MOTOR NOM CURR
Nominal motor current from motor rating plate. Values for this
parameter range from 0.5* I
the ACS140.
Default value: I
9907
MOTOR NOM FREQ
Nominal motor frequency from motor rating plate.
Range: 0 - 300 Hz
Default: 50 Hz
9908
MOTOR NOM SPEED
Nominal motor speed from motor rating plate.
Range 0 - 3600 rpm.
Default: 1440
4 =
MOTOR POT
5 =
HAND
6 =
PID CONTROL
7 =
PREMAGN
)
FACTORY MACRO
- 1.5* I
N
N
ac.maher.co.ir
-
AUTO
Selection for 400V units:
380, 400, 415, 440, 460, 480 V
, where I
is nominal current of
N
N
The table continues on the next page.