Group 15: Analogue Output - ABB ACS140 User Manual

Frequency converter
Hide thumbs Also See for ACS140:
Table of Contents

Advertisement

Group 15: Analogue Output

Analogue output is used to output the value of any parameter of the
Operating Data group (Group 1) as a current signal. Output current minimum
and maximum values are configurable, as are the allowed minimum and
maximum values for the observed parameter.
If analogue output content maximum value (parameter 1503) is set to less
than minimum value (parameter 1502), output current is inversely
proportional to the value of the observed parameter.
Code Description
1501 AO CONTENT
Content for analogue output. Number of any parameter of the Operating Data
group (Group 01).
1502 AO CONTENT MIN
Analogue output content minimum. Display and default value depends on
parameter 1501.
1503 AO CONTENT MAX
Analogue output content maximum. Display and default value depends on
parameter 1501.
1504 MINIMUM AO
Minimum output current.
1505 MAXIMUM AO
Maximum output current.
1506 AO FILTER
Filter time constant for AO.
1505
1504
1505
1504
Figure 5
Analogue output scaling.
AO (mA)
1502
AO (mA)
1503
ac.maher.co.ir
1503
AO content
1502
AO content