Application Macro Factory (0)

This macro is intended for applications where there is no control panel
available. It provides a general purpose 2-wire I/O configuration.
The value of parameter 9902 is 0. DI4 is not connected.
Input signals
• Start, stop and direction (DI1,2)
• Analogue reference (AI1)
• Constant speed 1 (DI3)
• Ramp pair 1/2 selection (DI5)
mA
*Note! DI 4 is used to configure ACS140. It is read only once when power is
connected. All parameters marked with * are determined by the DI4 input.
Factory (0) parameter values:
*1001
1
EXT
COMMANDS
1002
2
EXT
COMMANDS
1003
DIRECTION
1102
1/
2
EXT
EXT
SEL
1103
1
EXT REF
SELECT
Output signals
• An. output AO: Frequency
• Relay output 1: Fault
• Relay output 2: Running
Control
Function
Terminals
1 SCR
2 AI 1
External reference 1; 0...10 V <=> 0...50 Hz
3 AGND
4 10 V
Reference voltage 10 VDC
5 AI 2
Not used
6 AGND
7 AO
Output frequency 0...20 mA <=> 0...50 Hz
8 AGND
9 +12 V +12 VDC
10 DCOM
11 DI 1
Start/Stop. Activate to start ACS140
12 DI 2
Fwd/Rev. Activate to reverse rotation direction
13 DI 3
Constant speed 1. Default: 5Hz
14 DI 4
Leave unconnected!*
15 DI 5
Ramp pair selection. Activate to select ramp pair 2.
Defaults: 5 s (ramp pair 1), 60 s (ramp pair 2)
16 RO 1A
17 RO 1B
18 RO 2A
19 RO 2B
2 (DI1,2)
0 (
NOT SEL
3 (
REQUEST
6 (
1)
EXT
1 (
1)
AI
ac.maher.co.ir
1106
2
EXT REF
)
*1201
CONST SPEED SEL
)
1601
RUN ENABLE
2105
PREMAGN SEL
2201
/
1/2
ACC
DEC
DIP switch S1
S1:1:U
Relay output 1
Fault: open
Relay output 2
Running: closed
0 (
SELECT
KEYPAD
3 (
3)
DI
0 (
NOT SEL
0 (
NOT SEL
5 (
5)
SEL
DI
)
)
)