Application Macro Premagnetise

This macro is intended for those applications where the drive must start very
quickly. Building up the flux in the motor always takes time. With the
Premagnetise Macro, this delay can be eliminated.
The value of parameter 9902 is 7.
Input signals
• Start, stop and direction (DI1,2)
• Analogue reference (AI1)
• Preset speed selection (DI3,4)
• Premagnetise (DI5)
mA
*Constant speed selection: 0 = open, 1 = connected
DI3
DI4
Output
0
0
Reference through AI1
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
Premagnetise parameter values:
1001
1
EXT
COMMANDS
1002
2
EXT
COMMANDS
1003
DIRECTION
1102
1/
2
EXT
EXT
SEL
1103
1
EXT REF
SELECT
Output signals
• An. output AO: Frequency
• Relay output 1: Fault
• Relay output 2: Running
Control
Function
Terminals
1
SCR
2
AI 1
External reference1: 0...10 V <=> 0...50 Hz
3
AGND
4
10 V
Reference voltage 10 VDC
5
AI 2
Not used
6
AGND
7
AO
Output frequency 0...20 mA <=> 0...50 Hz
8
AGND
9
+12 V
+12 VDC
10 DCOM
11 DI 1
Start/Stop: Activate to start ACS140
12 DI 2
Fwd/Rev: Activate to reverse rotation direction
13 DI 3
Constant speed select*
14 DI 4
Constant speed select*
15 DI 5
Premagnetise: Activate to start premagnetising
16 RO 1A
17 RO 1B
18 RO 2A
19 RO 2B
2 (
1,2)
DI
0 (
)
NOT SEL
3 (
)
REQUEST
6 (
1)
EXT
1 (
)
KEYPAD
ac.maher.co.ir
1106
2
EXT REF
SELECT
1201
CONST SPEED SEL
1601
RUN ENABLE
2105
PREMAGN SEL
2201
/
1/2
ACC
DEC
SEL
DIP switch S1
S1:1:U
Relay output 1
Fault: open
Relay output 2
Running: closed
0 (
)
KEYPAD
7 (
3,4)
DI
0 (
)
NOT SEL
5 (DI5)
0 (
)
NOT SEL