Group 16: System Controls

Code Description
1601 RUN ENABLE
Selects the source of the run enable signal.
0 =
NOT SEL
The ACS140 is ready to start without an external run enable signal.
1...5 = DI1 ... DI5
To activate the run enable signal, the selected digital input must be activated. If
the voltage drops and deactivates the selected digital input, the ACS140 will
coast to stop and not start until the run enable signal resumes.
6 =
COMM
The run enable signal is given through serial communication.
1602 PARAMETER LOCK
0 =
LOCKED
Control panel START/STOP and REVERSE buttons and parameter modification
disabled. Parameter value viewing is allowed.
1 =
OPEN
Panel operations are allowed.
2 =
NOT SAVED
Modified values not stored in permanent memory.
Note! Option 0 (
Note! This parameter is not affected by macro selection.
1604 FAULT RESET SEL
Fault reset source.
Note! Fault reset is always possible with control panel.
0 =
KEYPAD ONLY
Fault reset is executed from the control panel keypad.
1...5 = DI1 ... DI5
Fault reset is executed from a digital input. Reset is activated by deactivating the
input.
6 =
/
START
STOP
Fault reset is activated by Stop command.
7 =
COMM
Fault reset is executed through serial communication.
1608 DISPLAY ALARMS
Controls the visibility of some of the alarms, see "Diagnostics" on page 81.
0 =
NO
Some of the alarms are suppressed.
1 =
YES
All of the alarms are enabled.
) can be selected only in remote mode.