Application Macro Motor Potentiometer
This macro provides a cost-effective interface for PLCs that vary the speed of
the drive using only digital signals.
The value of parameter 9902 is 4.
Input signals
• Start, stop and direction (DI1,2)
• Reference up (DI3)
• Reference down (DI4)
• Preset speed selection (DI5)
mA
*Note!
•
If both DI 3 and DI 4 are active or inactive, reference is kept stable.
•
Reference is stored during stop or power down condition.
•
Analogue reference is not followed when motor potentiometer is
selected.
Motor potentiometer parameter values:
1001
1
EXT
COMMANDS
1002
2
EXT
COMMANDS
1003
DIRECTION
1102
1/
2
EXT
EXT
SEL
1103
1
EXT REF
SELECT
Output signals
• An. output AO: Frequency
• Relay output 1: Fault
• Relay output 2: Running
Control
Function
Terminals
1
SCR
2
AI 1
Not used
3
AGND
4
10 V
Reference voltage 10 VDC
5
AI 2
Not used
6
AGND
7
AO
Output frequency 0...20 mA <=> 0...50 Hz
8
AGND
9
+12 V
+12 VDC
10 DCOM
11 DI 1
Start/Stop: Activate to start ACS140
12 DI 2
Forward/Reverse: Activate to reverse rotation
direction
13 DI 3
Reference up: Activate to increase reference*
14 DI 4
Reference down: Activate to decrease
reference*
15 DI 5
Constant speed 1
16 RO 1A
17 RO 1B
18 RO 2A
19 RO 2B
2 (
1,2)
DI
0 (
)
NOT SEL
3 (
)
REQUEST
6 (
1)
EXT
6 (
3
,4
)
DI
U
D
ac.maher.co.ir
1106
2
EXT REF
SELECT
1201
CONST SPEED SEL
1601
RUN ENABLE
2105
PREMAGN SEL
2201
/
1/2
ACC
DEC
SEL
Relay output 1
Fault: open
Relay output 2
Running: closed
0 (
)
KEYPAD
5 (
5)
DI
0 (
)
NOT SEL
0 (
)
NOT SEL
0 (
)
NOT SEL