2-stage automatic switch-off according to EnEV (Germany Energy Saving Act, EN 15232,
Chapter 5.1.2)
(only Monoblock devices)
The lighting does not switch off completely at first go. If no movement is detected, the
brightness reduces itself to 20% after the switch-off delay expires. If no further movement is
detected the lighting switches off completely after a further 5 minutes.
The brightness value of the intermediate stage (20% according to EnEV) and the time
duration until switch-off can be set via the app.
Switch-off warning according to DIN 18015
The light flashes 30 seconds before deactivation.
For a set switch-off delay under 60 seconds: 15 seconds before switch-off
For a set switch-off delay under 30 seconds: 5 seconds before switch-off
This function is required for stairwells in multifamily houses. The end of the illumination time
is indicated in a timely manner to extend the illumination duration through movement
detection or extension unit operation.
In the state of delivery of the presence detectors the switch-off warning is deactivated.
The switch-off warning can be activated/deactivated on the Monoblock devices with
®
Bluetooth
To activate the switch-off warning of the flex presence detector sensors, the following process is
to be carried out.
Unlock the manual transmitter during the first 10 minutes after connection of the presence
detector to the power via the IR remote control.
Then press the unlocking button again and then the push-button briefly 3 times in
succession for the brightness-value threshold 10 lux.
Finally press the locking button to save and finish the process.
To deactivate the switch-off warning, this process must be carried out again with the 2,000 lux
button on the remote control or the device reset via the reset button of the remote control.
System Manual 2CKA001473B9577
interface via the app.